- 0Your Inquiry cart is empty
AC Output | |||||
---|---|---|---|---|---|
115V Models | 230V Models | ||||
Power Levels crated at nominal inputs | 1000VA/ 700W;1700VA/ 1200W; 2500VA/ 1800W;3500VA/ 2400W; 4000VA/ 3200W | ||||
Output Voltage | 100V/110V/115V/120V Selectable | 200V/220V/230V/240V Selectable | |||
Voltage Waveform | Sine wave | ||||
Crest Factor | 5:1 | ||||
Output Frequency | 50/60Hz(selectable by using the remote set-up software) | ||||
Regulation | ±3% (output voltage adjustable by using the remote set-up software) | ||||
Transfer time (Models with AC input) | 2ms typical (Bypass to inverter mode) Zero (Inverter mode to bypass mode) | ||||
Over current protection | Over load alarm level 100% ~ 120% Over load shutdown level 120% ~ 190% (Adjustable by using the remote set-up software) | ||||
AC Input (optional input) | |||||
115V Models | 230V Models | ||||
Nominal Voltage | 100V/110V/115V/120V Selectable | 200V/220V/230V/240V Selectable | |||
Input Frequency | 47Hz ~ 65Hz, 50/60Hz auto-sensing | ||||
Efficiency | 97% (Normal mode) | ||||
Noise Filtering | Full time EMI/RFI filtering | ||||
Over current protection | By re-settable over current protector | ||||
Voltage Range | -30% ~ +33% for selected nominal voltage. | ||||
AVR Range (2 Bucks, 2 Boosts) | Enhanced Buck: +24% of selected nominal voltage Buck mode: +8% of selected nominal voltage Boost mode: -8% of selected nominal voltage Enhanced Boost: -20% of selected nominal voltage | ||||
Surge Protection (Only available when AC Input included) | 1000VA:216 Joules 1700VA ~ 4000VA:324 Joules | 1000VA:220 Joules 1700VA / 2500VA:440 Joules 3500VA / 4000VA:660 Joules | |||
DC Input | |||||
Voltage | 24Vdc(20Vdc ~ 32Vdc):1000VA / 1700VA 48Vdc(40Vdc ~ 64Vdc): 1000VA / 1700VA / 2500VA / 3500VA 72Vdc(60Vdc ~ 96Vdc): 1700VA / 2500VA / 3500VA 96Vdc(80Vdc ~128Vdc): 1700VA / 2500VA / 3500VA 108Vdc(90Vdc ~ 144Vdc):1700VA / 2500VA / 3500VA / 4000VA | ||||
Typical run time | Load <100%, No Limit 100%<Load<120%, 30 minutes typical 120%<Load<190%, 1 minute maximum 190%<Load, 0.25 second typical | ||||
Protection | Input polarity protection (by DC relay) DC fuse protection (60A or 120A, depends on DC voltage and VA rating) Over current protection (2KHz Switching, real time protection) Under voltage protection Over voltage protection (CPU control) | ||||
Monitoring | Smart monitoring & warning for failed battery | ||||
Communications & Management | |||||
Interface port | UPSilon2000 compatible; optional for RS232 and/or USB | ||||
Control panel | LCD or LED Selectable (Rack units with LCD only) | ||||
Audible alarm | Alarm on battery:Low battery & Battery over voltage Alarm on abnormal operation:Over load, Short-circuit, & Over heat | ||||
Green mode function (for models with AC input) | 1% to 14% of full load (adjustable by using the remote set-up software) The default setting is OFF. | ||||
Cooling fan control | Auto on / off, controlled by temperature & operation mode | ||||
Environmental and Safety | |||||
Operating Temperature | Up to 1500 meters:0℃ to 40℃ (32℉ to 104℉) | ||||
Transit/storage Temperature | -15℃ to 55℃ (5℉ to 131℉) | ||||
Relative Humidity | 5 - 95% non condensing | ||||
Operating Altitude | 0 ~ 3000 meters | ||||
Audible noise at 1M from surface of unit | ≦50 dBA | ||||
Safety Markings | CE | ||||
EMC | Class A, EN50091-2, FCC part15, IEC1000-2-2 | ||||
Isolation | 3KVac for 1 minute between DC input and AC output | ||||
Quality control system | ISO 9001 | ||||
Physical | |||||
Dimensions: Unit / Shipping D×H×W (cm) | Tower (ILT) | Rack (ILR) | |||
1000VA/ 1700VA/ 2500VA: 45 x 20 x 18 cm / 54 x 33 x 30 cm 3500VA/ 4000VA: 51 x 20 x 18/61 x 33 x 30 cm | 1000VA/ 1700VA/ 2500VA/ 3500VA: 3u x 45 cm / 59 x 33 x 59 cm 4000VA: 4u x 45 cm / 59 x 38 x 59 cm | ||||
Weight: Net / Gross (kg) | 1000VA:16 / 17 (kg) 1700VA:19 / 20 (kg) 2500VA:23 / 24 (kg) 3500VA:31 / 33 (kg) 4000VA:43 / 45 (kg) | 1000VA :20 / 24 (kg) 1700VA :26 / 30 (kg) 2500VA/ 3500VA :34 / 38 (kg) 4000VA:48 / 52 (kg) | |||
Packing | Export carton for each unit, 16 - 30 units per pallet |