Output | |||
---|---|---|---|
115V Models | 230V Models | ||
Power Levels crated at | 1100VA / 660W, 2200VA / 1350W, 3000VA / 1800W, | ||
nominal inputs | |||
Output Voltage | 100V/110V/115V/120V Selectable | 200V/220V/230V/240V Selectable | |
Voltage Waveform | Sine wave | ||
Crest Factor | 3:1 | ||
Output Frequency | Auto Select for 50/60Hz | ||
(Synchronized to Mains) | 47Hz ~ 55Hz for 50Hz nominal | ||
56Hz ~ 65Hz for 60Hz nominal | |||
Regulation (Nominal) | ±5% typical of nominal voltage (optional at ±8% AVR for wide I/P up to ±35%) | ||
Regulation (Batt. mode) | ±3% of selected output voltage (adjustable with the remote set-up software) | ||
Transfer time | Blackout 3ms typical | ||
Brownout 1ms typical | |||
Battery mode to Normal mode:1ms typical | |||
Over current protection | Over load alarm level 100% ~ 120% | ||
Over load shutdown level 120% ~ 190% | |||
(Adjustable with the remote set-up software) | |||
Input | |||
115V Models | 230V Models | ||
Nominal Voltage | 100V/110V/115V/120V Selectable | 200V/220V/230V/240V Selectable | |
Input Frequency | 47Hz ~ 65Hz, 50/60Hz auto-sensing | ||
Efficiency (Normal mode) | 97% | ||
Noise Filtering | Full time EMI/RFI filtering | ||
Over current protection | 1100VA:by AC fuse 2200VA ~ 3000VA:by re-settable over current protector | 110VA ~ 2200VA:by AC fuse 3300VA:by re-settable over current protector | |
Voltage Range | -20% ~ E27+24% for selected nominal voltage.E26 -29% ~ +33% adjustable with the remote set-up software | ||
AVR Range (2 Bucks, 2 Boosts) | Enhanced Buck: +15% of selected nominal voltage Buck mode: +5% of selected nominal voltage Boost mode: -5% of selected nominal voltage Enhanced Boost: -12.5% of selected nominal voltage | ||
Surge Protection | 1100VA:216 Joules 2200VA ~ 3000VA:324 Joules | 1100VA:220 Joules 2200VA:440 Joules 3000VA:660 Joules | |
Battery | |||
Battery type | Maintenance–free sealed, valve-regulated, Lead-Acid 800VA ~ 3300VA:12V, 7Ah, 4000VA:12V, 9Ah | ||
Voltage | 1100VA:24Vdc, (48Vdc Optional) 2200VA:48Vdc, 3300VA:72Vdc | ||
Typical backup time at half-load | No Limit | ||
Typical backup time at full load | No Limit | ||
Charging method | Smart pulse charging with two charging modes. Quick charging when battery is not fully charged, trickle charging when battery is 90% fully charged. | ||
Average charging current | 11 A at normal line and normal temperature | ||
Average charging voltage for each battery | Quick charging mo Trickle charging mode:13.2V ~13.9V adjustable with the remote set-up software.de:14V maximum. | ||
Protection | Over current protection (SCR control) Over charging voltage protection (SCR control) Thermal protection (CPU control) When temperature inside UPS is over 45℃, charger will stop charging for 2.5 minutes followed by an 1.5 minutes charging. The cycle will be repeated until the temperature is lower than 44℃. | ||
Monitoring | Smart monitoring & warning for failed battery or open-circuit battery. Auto-detection each time when power on or every 6 days. | ||
Communications & Management | |||
Standard Interface port | UPSilon2000 compatible. 800VA ~ 3000VA:RS232, optional for RJ45, USB. | ||
Optional Interface port | DB9, SNMP (external type) | ||
Control panel | LCD or LED Selectable | ||
Audible alarm | Alarm on battery:Low battery & Battery over voltage Alarm on abnormal operation:Over load, Short-circuit, & Over heat | ||
EBT (Estimation of Backup Time) system | Support for LCD display | ||
Green mode function (Auto-shutdown during blackout) | 1% to 14% of full load (adjustable with the remote set-up software) The default setting is OFF. | ||
Environmental and Safety | |||
Operating Temp. | Up to 1500 meters:0℃ to 40℃ (32℉ to 104℉) | ||
Transit/storage Temp. | -15℃ to 55℃ (5°F to 131°F) | ||
Relative Humidity | 5 - 95% non condensing | ||
Operating Altitude | 0 ~ 3000 meters | ||
Audible noise | ≦40 dBA (at 1M from surface of unit) | ||
Safety Markings | BSMI | CE | |
EMC | Class B, EN50091-2, FCC part15, IEC1000-2-2 | ||
Quality control system | ISO 9001 | ||
Physical | |||
Dimensions: (D×H×W) Unit / Shipping | 45 x 20 x 18 (cm) / 54 x 33 x 30 (cm) | ||
Weight:Net / Gross (kg) | 1000VA:15 / 16 (kg), 2200VA:25 / 26 (kg), 3300VA:36 / 37 (kg) | ||
Packing | Export carton for each unit, 16 - 30 units per pallet |