Long-Run 1KVA~3KVALong-Run 1KVA~3KVA

Availability: In stock

Model number: UHT-L-1KVA-3KVA

Inquiry
Quantity
ONLINE UPS " Tower Long-Run Ver. " UHT-L 1KVA ~ 3KVA

Feature :

  • Multiple Microprocessor design base
  • Detachable control panel with LCD
  • Unity input power factor and wide input range
  • Robust design with output transformer
  • True sine-wave double conversion on-line UPS
  • DC start and automatic self-diagnostic function
  • RS232 communication port and built-in SNMP slot
  • High efficiency design to save electricity
  • Low heat dissipation in long term operation
  • Designed to operate under harsh environment
  • Enhanced protections against lighting surges, disturbances etc..
Technical specification:

(1) 10-120KVA specification:

ModelPV3310iiPV3315iiPV3320iiPV3330iiPV3340iiPV3360iiPV3380iiPV33100iiPV33120ii
Capacity10kVA15kVA20kVA30kVA40kVA60kVA80kVA100kVA120kVA
System
Output PF 0.8(lag)
System efficiency  (inverter mode)92%(@100% load) ;90% @50%load;
System efficiency  (ECO mode)98%(@100%load)
Maximum leakage current100(mA)
MTBFAbove 200,000hours
Dry contact Standard: 3 types signal(BAT. low,battery mode,bypass /failure);
Optional:14 dry contact ; output: 12Vdc 80mA
Communication interfaceStandard RS232,optional: RS485 / MODBUS
Operation temperature0 ~ 40 °C
Humidity95 % (non-condense)
CoolingForced air(speed varying according to load percent)
Max. altitudeWithin 1000m(every 100increase,capacity decrease -1%),Maximum 4000m
Noise (dB)52 ~ 58
IP protectionIP20
(EN 60529)
Input/output wayBottom /rear
Safety standardsafety:GB4943 ,EN 50091-1;EMI:GB7260.2,GB/T 17626.2~5EMC, EN 50091-2
Physical
W *D*H(mm)600*600*1280800*800*1480800*800*1800
Weight(Kg)195210220305340500600800950
AC input
Rated voltage 380/400/415VAC  Three-phase four-wires
Input voltage range± 15 %- ± 25 % adjustable)
Rate frequency50 / 60 Hz  auto-sense
Frequency range50/60Hz+/-5Hz
Input soft start function0 - 100%,10-300s(settable)
Input power factorReachable 0.99(plus harmonic filter)
Input current harmonic component(THDi )Can <5%(plus harmonic filter)
Max. input current [A]1827365472108144180216
The output characteristic of the rectifier
Maintain the voltage (20°C)Battery type1 and 2 :V =435Vdc (2.266 x el.)
Battery type 3 :V =424Vdc (2.21 x el.)
 Battery type 0:the voltage value between type 1and 2,
Voltage regulating range: V =400~460Vdc
Charging voltage (20°C)Battery type1 and 2 :V (%recharging<95%) = 445Vdc (2.32 x el.)
Battery type 3 :V (%recharging<95%) = 460Vdc (2.4 x el.)
Battery type 0: the voltage value between type 1and 2,
Voltage regulating range: V =400~460Vdc
The highest charging voltage445V
The charger output voltage regulation accuracy1%
DC ripple voltage component≤1%
Battery
Unit number(rated voltage)384VDC(360-384v,selectable)
Charging current settings0.1C(battery capacity)
The battery discharge end voltageBattery type 1,2 and 3:no-load discharge current,V min=346 [V dc]
Battery type 1,2 and 3:output current =Ah capacity,V min=316 [V dc]
Battery type 1,2 and 3:output current >Ah capacity,V min=306 [V dc]
Battery type 0: the factory set the default values,V min=320 [V dc]  
Regulating range: V min =300~360[V dc]
Inverter output
Rated capacity  [kVA]10152030406080100120
Rated power  [kW]81216243248648096
Rated voltage  [V] 380/400/415VAC  three-phase four-wire
Rated current  [A]12182436487296120144
Phase voltage setting200 ~ 244 V (control board)
Peak factor03:01
Voltage phase shift (degrees)       100% balanced load± 1'
Voltage phase shift (degrees)± 2'
100% unbalanced load
Phase voltage difference         100% balance load± 1 %
Phase voltage difference         100% unbalanced load± 3 %
(THD v)<2% (linear load), <5%(non-linear load)
Steady-state voltage stability± 1 %
Transient voltage response± 5 % within 10ms
Rated frequencySame as input
Frequency stabilityWhen asynchronous,± 0.5 %;synchronization,± 2 %
(can be set to ± 1~5 %,by the panel operation)
Overload  600’ / 10’ / 1’ (110/125/150% rated current)
Short circuit 0.1sDouble input
Inverter efficiency(load 100%)98%
Bypass
Rated capacity  [kVA]10152030406080100120
Rated voltage  [V] 380/400/415VAC Three-phase four-wires
Input voltage range±15 %(can be adjusted from the control panel ± 10 %,± 20%)
Rated frequency       [Hz]50 / 60
Frequency range±2 %(can be adjusted from the control panel ± 5 %)
“STAND-BY ON”(Eco mode, the bypass switch to inverter)transfer time2~5ms
Inverter/bypass transfer time<1ms
Overload10’/1’/18” (150/175/200% Rated current)
Standard configurationFeed flow protection, bypass independently isolated

 

(2) 160-400KVA product specification parameter table:

ModelPV33160 iiPV33200 iiPV33250 iiPV33300 iiPV33350 iiPV33400 ii
Capacity160kVA200kVA250kVA300kVA350kVA400kVA
6 pulse12 pulse6 pulse12 pulse6 pulse12 pulse6 pulse12 pulse6 pulse12 pulse6 pulse12 pulse
System parameter
Output power factor 0.8(lag)
Overall efficiency (normal model)                 Load 100%94%
Load 50%92%
Overall efficiency:
(ECO mode)              Load 100%
98%
Maximum leakage current(mA)100
Standby economic modelStandard functions
Mean time before failure(MTBF)Above 200,000 hours
Dry contact signal Standard three control signal (battery low,battery discharge,bypass/breakdown);
Optional 14 control signal;output 12Vdc 80mA
Computer monitors portStandard S232,optional ODBUS
Running temperature0 ~ 40 °C
Maximum relative humidity95 % (non-condensing)
CoolingForced ventilation (fan speed changing with load)
Maximum altitude1000m rated power(Rising 100m lower 1%) maximum 4000m
Noise dB54 ~ 62
Protection classIP20
(EN 60529)
Inlet and outlet of the wire wayBottom /rear
Safety standard Safety: GB4943,EN 50091-1;electromagnetic compatibility: GB7260.2,
GB/T 17626.2~5EMC,EN 50091-2
Physical parameter
Wide (mm)1100 14001100140014001400140014001600160016001600
Deep*high (mm)800*18001000*20001100*2000
Weight(kg)1200 15501350175015001950165021501850240021002700
The input rectifier features
Rated voltage 380/400/415VAC  Three-phase four wires
Voltage range± 15 % (± 25 % adjustable)
Rated frequency50 / 60 Hz automatic identification
Frequency range45 ~ 65
Input power
slow start function
Yes,0 - 100%,can be set to 10-300 seconds
Input power factors cosφReachable 0.99(plus harmonic filter)
Input current harmonic component(THDi )can<5%(plus harmonic filter)
Max.input current [A]250315400500550630
The output characteristic of the rectifier
Maintain the voltage (20°C)Battery type1 and 2 :V =435Vdc (2.266 x el.)Battery type1 and 2 :  
V =544Vdc (2.266 x el.)
Battery type 3 :V =424Vdc (2.21 x el.)Battery type 3 :      
V =530Vdc (2.21 x el.)
Battery type 0:the voltage value between type 1 and 2,
Voltage regulating range: V =400~460Vdc
Battery type 0:the voltage value between type 1 and 2, Voltage regulating range:
V =500~575Vdc
Charging voltage (20°C)Battery type1 and 2 :V (%recharging<95%)=445Vdc (2.32 x el.)Battery type1 and 2 : V (%recharging<95%)
=557Vdc (2.32 x el.)
Battery type 3 :V (%recharging<95%)=460Vdc (2.4 x el.)Battery type 3 :V (%recharging<95%)
=576Vdc (2.4 x el.)
Battery type 0:the voltage value between type 1 and 2,
Voltage regulating range: V =400~460Vdc
Battery type 0:the voltage value between type 1 and 2, Voltage regulating range:
V =500~575Vdc
The highest charging voltage445V556V
The charger output voltage regulation accuracy1%
DC ripple voltage component≤1%
Battery
Unit number(rated voltage)192 units(384VDC)240 units(480VDC)
Charging current settings0.1 C(battery capacity)
The battery discharge end voltageBattery type 1,2 and 3:no-load discharge current,
Vmin=346 [V dc]
Battery type 1、2 and 3:no-load discharge current,Vmin=433 [V dc]
Battery type1,2 and 3:output current =Ah capacity,
Vmin=316 [V dc]
Battery type 1、2 and 3:
output current =Ah capacity,
Vmin=395 [V dc]
Battery type 1,2,3:output current >Ah capacity,
Vmin=306 [V dc]
Battery type 1、2 and 3:
output current >Ah capacity,
Vmin=383 [V dc]
Battery type 0:the factory set the default values,Vmin=320 [Vdc]  Regulating range: Vmin =300~360V[V dc]Battery type 0:the factory set the default values,Vmin=400 [V dc] Regulating range:
Vmin =375~450V[V dc]
Inverter output
Rated capacity  [kVA]160200250300350400
Rated power  [kW]128160200240280320
Rated voltage  [V] 380/400/415VAC  three-phase four-wire
Rated current  [A]195243304365426486
Phase voltage setting200 ~ 244 V (control board)
Peak factor03:01
Voltage phase shift (degrees)       100% balanced load± 1'
Voltage phase shift (degrees)
100% unbalanced load
± 2'
Phase voltage difference         100% balance load± 1 %
Phase voltage difference         100% unbalanced load± 3 %
THD v<2% (linear load), <5%(non-linear load)
Steady-state voltage stability± 1 %
Transient voltage response± 5 % within 10ms
Rated frequencySame as input
Frequency stabilityWhen asynchronous,± 0.5 %;synchronization,± 2 %
can be set to ± 1~5 %,by the panel operation)
Overload  600’ / 10’ / 1’ (110/125/150% rated current)
Short circuit 0.1sDouble input
Inverter efficiency    (load 100%)98%
Bypass
Rated capacity  [kVA]160200250300350400
Rated voltage  [V] 380/400/415VAC  three-phase four-wires
Input voltage range±15 %(can be adjusted from the control panel± 10 %,± 20%)
Rated frequency       [Hz]50 / 60
Frequency range±2 %(can be adjusted from the control panel± 5 %)
“STAND-BY ON”(Economic mode, the bypass switch to inverter)conversion time2~5ms
Inverter/bypass transfer time<1ms
Overload10’/1’/18” (150/175/200% rated current)
Standard configurationFeed flow protection, bypass independently isolated


NOTE: 120VAC power grid 10-200kVA are available;