- 0Your Inquiry cart is empty
MODEL | UKR1000 | UKR1000L | UKR2000 | UKR2000L | UKR3000 | UKR3000L |
---|---|---|---|---|---|---|
INPUT | ||||||
Voltage (Vac) | 120-295 | |||||
Frequency (Hz) | 50/60± 10% (50/60Hz auto-sensing) | |||||
Power Factor | ≧ 0.99 | |||||
THDi | < 5% | |||||
OUTPUT | ||||||
Capacity(VA) | 1000 | 2000 | 3000 | |||
AC/AC Efficiency | 92% | 93% | 94% | |||
Power Factor | 0.9 (1.0 optional) | |||||
Voltage(Vac) | 208/220/230/240±1% (settable on display panel) | |||||
Frequency(Hz) | 50/60±0.1 (battery mode) | |||||
THDv | THD < 3% (linear load); THD < 5% (nonlinear load) | |||||
Transfer Time | 0 | |||||
Overload | 101%~115% for 1 min, 116%~133% for 1s, above 134% for 200ms | |||||
BATTERY | ||||||
Voltage(Vdc) | 24 | 36 | 48 | 72 | 72 | 96 |
BATT Type | 2x9Ah12V | External | 4x9Ah12V | External | 6x9Ah12V | External |
Charger Current (A) Max. | 1 | 4 | 1 | 4 | 1 | 4 |
OTHER | ||||||
Communication Interface | RS232 + UPS + EPO (RS485,Dry contact and SNMP adapter are optional) | |||||
Display | LCD | |||||
Alarm | Low battery,abnormal AC input,UPS failure,etc. | |||||
Protection | Low battery, overload, short-circuit and over temperature, etc. | |||||
Noise(dB) | < 50 | < 55 | ||||
Working Temperature | -5 ~ 40℃ | |||||
Relative Humidity | 0 ~ 95%, No condensation | |||||
Dimension(WxDxH) mm | 438x420x2U | 438x420x2U(UPS)+ 438x420x2U (Battery pack) | 438x420x2U | 438x420x2U(UPS)+ 438x420x2U (Battery pack) | 438x420x2U | |
Weight (kg) | 11.5 | 7 | 8+14 | 9.9 | 8.5+20 | 10 |